002522-387-G
PRODUCT CODE
1
2
3
4
5
6
7
8
9
10
Note that not all options are available on all models!
1 :- Enclosure 4 = Ex ia (Intrinsically Safe)
R = Ex d
A = Weatherproof
F = Factory Mutual approved
2 :- Model, 387 = Gauge and Absolute Pressure
3 :- Electrical Entry 1 = M20 Internal
2 = ½" NPT Internal
4 :- Wetted Parts R = All 316 Stainless Steel
S = 17-4PH or 15-5 PH Sensor, 316 Process connection
T = All Monel (NACE)
U = All Hastelloy (NACE)
C = Hastelloy sensor, 316 Process connection
5 :- Ranges (Bar) DA = 1 D2 = 2 DE = 6
EA = 10 EB = 16 ED = 40
FA = 100 FD = 400 FE = 600
GA = 1000
6 :- Pressure Reference G = Gauge
A = Absolute
7 :- Signal Output 6 = 4 – 20 mA - 50 Volt Isolation
M = 4 – 20 mA - 500 Volt Isolation
8 :- Process Connection J = ½ " NPT External
N = G ½"A to ISO 228
V = “Autoclave” High pressure connections
9 :- Options and Treatments Codes on Application
10 :- Special Engineering Codes on Application
DC
DC
HAZARDOUS AREA NON-HAZARDOUS AREA
LOAD
LOAD
35V(MAX) +DC
0V
0V
0V
4mm EARTH
1 ohm MAX
4mm EARTH
1 ohm MAX
2
* TO AVOID SPURIOUS SHUNT CURRENTS
IN THE BARRIER,THE MAX VOLTAGE
SHOULD BE LIMITED TO APPROX 27.5V
28V +
28V + *
28V
300
28V
300
10V
50
4mm
1 ohm MAX
1
2
3
4
Nb ALL SHUNT ZENER BARRIER
SYSTEMS REQUIRE AN IS EARTH
WHEN USED WITH MODEL 4-387.
SIGNAL CODE 6 OR 7 IS NOT
NECESSARY WITH SIGNAL CODES
M OR N.
METHOD 1
BARRIER WITH EARTH RETURN.
LOAD IS FLOATING WITH RESPECT
TO EARTH.
METHOD 2
BARRIER WITH 10V/50ohm RETURN.
LOAD MAY BE EARTHED.
METHOD 3
ACTIVE ZENER BARRIER GIVES
HIGHER POWER CAPABILITY AT
LOAD.
TYPICAL MODELS: MTL 702.
PEPPERL AND FUCHS
ZG30Ex.
Fig 1
EXTERNAL LOAD Kilo hm
0
5
10
15
20
25
45
30
35
40
1.6
1.4
1.2
1
0.8
0.6
0.4
0
0.2
VOLTAGE v LOAD
Voltage to be within triangular area
Fig 2